ecometertemplatebuilder
CA ecoMeter Template Builder

The ecoMeter Template Builder allows you to create and modify device templates and export them to ecoMeter Probes where that can be used to define the devices to be polled. The following protocols are supported:
  • SNMP
  • IPMI
  • WMI
  • BACnet
  • Modbus
  • EnergyWise

  • Upgrades

    To upgrade from an earlier version, add the 4.20 version of the Template Builder package to Hub archives. Then deploy the package to the same machine running the UMP. After deployment, add the ecoMeterTemplateBuilder monitoring portlet to a UMP page.
    An upgrade replaces any templates of the same name.

    Enhancements

    OIDs in Value Expressions

    An error occurred when a device or ecoMeter OID was referenced in a value expression. This error has been corrected.

    BACnet Service Type

    In order to help resolve BACnet polling errors, the Service Type attribute was added to BACnet templates. This attribute allows you to select one of two services that uses to communicate with the device:
  • ReadPropertyMultiple
  • Who-Is

  • The service type that you select must be supported on the BACnet device, however most devices support both services. If the device does support both services, you can select either one. If you experience polling errors with the one service, try polling the devices with the other service.

    Variable Units of Measure

    Unit of measure corrections were made to variables in the following tables:
  • SvrTable
  • The unit for the SvrPower variable was changed from kilowatts to watts.
  • RackPDUTable
  • The unit for the following variables was changed from kilowatt to kilovolt-ampere:
    RackPduApprntPwrPhaseA
    RackPduApprntPwrPhaseB
    RackPduApprntPwrPhaseC

    Third-Party Licenses


    Licensing restrictions prevent CA ecoMeter from packaging third-party libraries required for polling WMI devices. These libraries are provided in the ecometer3rdpartylibs archive package which must be added to the robots where the ecoMeter Probe is deployed. After adding the archive package, deactivate and then reactivate the CA ecoMeter Template Builder Probe so that the third-party JARs are loaded.
    Revision history
    Date Description State Version
    12.12.2014 See Enhancements section. 4.30
    27.10.2014 Added support for Nimsoft 8.0 and for exports of templates from Linux versions. 4.20
    28.07.2014 Added support for IMPI and WMI templates, changing SNMP version in SNMP templates, and importing and exporting data entry forms. Also added support for NMS 7.5 and 7.6 4.10
    25.03.2014 Added support for SNMP automatic discovery, data entry forms, and templates 4.00
    24.02.2014 Ability to support servers and storage devices via SNMP. This includes new portlets for showing reports for servers and storage devices’ energy efficiency. Enhancements to the SNMP auto-discovery, introduction of data entry form and user-friendly way for indicating polling failures. 4.00
    09.01.2013 Initial version 3.10
    Requirements
    Platform: Please refer to the Platform Support Matrix located in the Download section of http://support.nimsoft.com
    Software: Java version 1.6.x, NMS 7.6 or 8.0,CA Unified Management Portal 8.0
    Hardware: None